Dual Voltage And Single Voltage Output Setup For UPS
6KVA UPS (Uninterruptible Power Supply) Dual Voltage And Single Voltage Output
Hardwire UPS Setup 1: Generic example of installation of hardwire UPS and step down transformer in correlation to main panel (before UPS), sub panel (after UPS), and outlets (after sub panel).
UPS: 6000 VA / 4200 Watt Battery Backup Uninterruptible Power Supply (UPS) And 5 Tier Active Power Conditioner https://www.backupbatterypower.com/collections/frontpage/products/6kva-double-conversion-battery-backup-power-ups MAIN PANEL INPUT: 208 Volts, 40 Amp Dedicated Circuit, 40 Amp Breaker (125% Of Continuous Load) SUB PANEL OUTPUT: 208 Volts, 30 Amp Dedicated Circuit, 30 Amp Breaker (125% Of Continuous Load) |
|
STEP DOWN TRANSFORMER: C1F1C0WES - 1KVA (INPUT: 120/208/240/277 | OUTPUT: 120/240) http://www.alliedelec.com/hammond-power-solutions-c1f1c0wes/70191818/ INPUT: 208 Volts OUTPUT: 120 Volts |
Hardwire UPS Setup 2: Generic example of installation of hardwire UPS (no step down transformer) in correlation to main panel (before UPS), sub panel (after UPS), and outlets (after sub panel).
UPS: 6000 VA / 4200 Watt Battery Backup Uninterruptible Power Supply (UPS) And 5 Tier Active Power Conditioner https://www.backupbatterypower.com/collections/frontpage/products/6kva-double-conversion-battery-backup-power-ups MAIN PANEL INPUT: 208 Volts, 40 Amp Dedicated Circuit, 40 Amp Breaker (125% Of Continuous Load) SUB PANEL OUTPUT: 208 Volts, 30 Amp Dedicated Circuit, 30 Amp Breaker (125% Of Continuous Load) |
10KVA UPS (Uninterruptible Power Supply) Dual Voltage And Single Voltage Output
Hardwire UPS Setup 3: Generic example of installation of hardwire UPS and step down transformer in correlation to main panel (before UPS), sub panel (after UPS), and outlets (after sub panel).
UPS: 10000 VA / 7000 Watt Battery Backup Uninterruptible Power Supply (UPS) And 5 Tier Active Power Conditioner https://www.backupbatterypower.com/collections/frontpage/products/10kva-double-conversion-battery-backup-power-ups MAIN PANEL INPUT: 208 Volts, 60 Amp Dedicated Circuit, 60 Amp Breaker (125% Of Continuous Load) SUB PANEL OUTPUT: 208 Volts, 40 Amp Dedicated Circuit, 40 Amp Breaker (125% Of Continuous Load) |
|
STEP DOWN TRANSFORMER: C1F003WES – 3KVA (INPUT: 120/208/240/277 | OUTPUT: 120/240) http://www.alliedelec.com/hammond-power-solutions-c1f003wes/70191821/ INPUT: 208 Volts OUTPUT: 120 Volts |
Hardwire UPS Setup 4: Generic example of installation of hardwire UPS (no step down transformer) in correlation to main panel (before UPS), sub panel (after UPS), and outlets (after sub panel).
UPS: 10000 VA / 7000 Watt Battery Backup Uninterruptible Power Supply (UPS) And 5 Tier Active Power Conditioner https://www.backupbatterypower.com/collections/frontpage/products/10kva-double-conversion-battery-backup-power-ups MAIN PANEL INPUT: 208 Volts, 60 Amp Dedicated Circuit, 60 Amp Breaker (125% Of Continuous Load) SUB PANEL OUTPUT: 208 Volts, 40 Amp Dedicated Circuit, 40 Amp Breaker (125% Of Continuous Load) |
15KVA UPS (Uninterruptible Power Supply) Dual Voltage And Single Voltage Output
Hardwire UPS Setup 5: Generic example of installation of hardwire UPS and step down transformer in correlation to main panel (before UPS), sub panel (after UPS), and outlets (after sub panel).
UPS: 15000 VA / 10500 Watt Battery Backup Uninterruptible Power Supply (UPS) And 5 Tier Active Power Conditioner https://www.backupbatterypower.com/collections/frontpage/products/15kva-double-conversion-battery-backup-power-ups MAIN PANEL INPUT: 208 Volts, 80 Amp Dedicated Circuit, 80 Amp Breaker (125% Of Continuous Load) SUB PANEL OUTPUT: 208 Volts, 70 Amp Dedicated Circuit, 70 Amp Breaker (125% Of Continuous Load) |
|
STEP DOWN TRANSFORMER: C1F003WES – 3KVA (INPUT: 120/208/240/277 | OUTPUT: 120/240) http://www.alliedelec.com/hammond-power-solutions-c1f003wes/70191821/ INPUT: 208 Volts OUTPUT: 120 Volts |
Hardwire UPS Setup 6: Generic example of installation of hardwire UPS (no step down transformer) in correlation to main panel (before UPS), sub panel (after UPS), and outlets (after sub panel).
UPS: 15000 VA / 10500 Watt Battery Backup Uninterruptible Power Supply (UPS) And 5 Tier Active Power Conditioner https://www.backupbatterypower.com/collections/frontpage/products/15kva-double-conversion-battery-backup-power-ups MAIN PANEL INPUT: 208 Volts, 80 Amp Dedicated Circuit, 80 Amp Breaker (125% Of Continuous Load) SUB PANEL OUTPUT: 208 Volts, 70 Amp Dedicated Circuit, 70 Amp Breaker (125% Of Continuous Load) |
20KVA UPS (Uninterruptible Power Supply) Dual Voltage And Single Voltage Output
Hardwire UPS Setup 7: Generic example of installation of hardwire UPS and step down transformer in correlation to main panel (before UPS), sub panel (after UPS), and outlets (after sub panel).
UPS: 20000 VA / 14000 Watt Battery Backup Uninterruptible Power Supply (UPS) And 5 Tier Active Power Conditioner https://www.backupbatterypower.com/collections/frontpage/products/20kva-double-conversion-battery-backup-power-ups MAIN PANEL INPUT: 208 Volts, 125 Amp Dedicated Circuit, 125 Amp Breaker (125% Of Continuous Load) SUB PANEL OUTPUT: 208 Volts, 90 Amp Dedicated Circuit, 90 Amp Breaker (125% Of Continuous Load) |
|
STEP DOWN TRANSFORMER: C1F003WES – 3KVA (INPUT: 120/208/240/277 | OUTPUT: 120/240) http://www.alliedelec.com/hammond-power-solutions-c1f003wes/70191821/ INPUT: 208 Volts OUTPUT: 120 Volts |
Hardwire UPS Setup 8: Generic example of installation of hardwire UPS (no step down transformer) in correlation to main panel (before UPS), sub panel (after UPS), and outlets (after sub panel).
UPS: 20000 VA / 14000 Watt Battery Backup Uninterruptible Power Supply (UPS) And 5 Tier Active Power Conditioner https://www.backupbatterypower.com/collections/frontpage/products/20kva-double-conversion-battery-backup-power-ups MAIN PANEL INPUT: 208 Volts, 125 Amp Dedicated Circuit, 125 Amp Breaker (125% Of Continuous Load) SUB PANEL OUTPUT: 208 Volts, 90 Amp Dedicated Circuit, 90 Amp Breaker (125% Of Continuous Load) |